Beskrivelse

Product description

Description8 port Fast-Ethernet-Switch, managed, software Layer 2 Enhanced, for DIN rail store-and-forward-switching, fanless design
Port type and quantity8 ports in total; 1. uplink: 100BASE-FX, MM-SC; 2. uplink: 100BASE-FX, MM-SC; 6 x standard 10/100 BASE TX, RJ45
TypeRS20-0800M2M2TDBEHH08.0.
Order No.RS20-0800M2M2TDBEHH08.0.

More Interfaces

Power supply/signaling contact1 x plug-in terminal block, 6-pin
V.24 interface1 x RJ11 socket
USB interface1 x USB to connect the AutoConfiguration Adapter ACA21-USB

Network size - length of cable

Multimode fiber (MM) 50/125 µm0 - 5000 m, 8 dB link budget at 1300 nm, A = 1 d/km, 3 dB reserve, B = 800 MHz x km
Multimode fiber (MM) 62.5/125 µm0 - 4000 m, 11 dB link budget at 1300 nm, A = 1 dB/km, 3 dB reserve, B = 500 MHz x km

Network size - cascadibility

Line - / star topologyany
Ring structure (HIPER-Ring) quantity switches50 (reconfiguration time < 0.3 sec.)

Power requirements

Operating voltage12/24/48 V DC (9,6-60) V and 24 V AC (18-30) V (redundant)
Current consumption at 24 V DC321 mA
Current consumption at 48 V DC161 mA
Power output in Btu (IT) h26.3

Software

ManagementSerial interface, web interface, SNMP V1/V2, HiVision file transfer SW HTTP/TFTP
DiagnosticsLEDs, log-file, relay contact, RMON, port mirroring 1:1, topology discovery 802.1AB, address conflict detection, network error detection, SFP diagnostic [temperature, optical input and output power (µW and dBm)], Trap for configuration saving and changing, duplex mismatch detection, disable learning.
ConfigurationComand line interface (CLI), TELNET, BootP, DHCP, DHCP option 82, HIDiscovery, easy device exchange with auto-configuration adapter ACA21-USB (automatic software and/or configuration upload), automatic invalid configuration undo, configuration signature (water marking)
SecurityPort Security (IP und MAC) with multiple addresses, SNMP V3 (no encryption)
Redundancy functionsHIPER-ring (ring structure), MRP (IEC-ring functionality), RSTP 802.1D-2004, redundant network/ring coupling, MRP and RSTP in parallel, redundant 24 V power supply
FilterQoS 4 classes, port priorisation (IEEE 802.1D/p), VLAN (IEEE 802.1Q), shared VLAN learning, multicast (IGMP Snooping/Querier), multicast detection unknown multicast, broadcastlimiter, fast aging
Industrial ProfilesEtherNet/IP and PROFINET (2.2 PDEV, GSDML stand-alone generator, automatic device exchange) profiles included, configuration and diagnostic via automation software tools like e.g. STEP7, or Control Logix
Time synchronisationSNTP server, PTP / IEEE 1588
Flow controlFlow control 802.3x, port priority 802.1D/p, priority (TOS/DIFFSERV)
PresettingsStandard

Ambient conditions

Operating temperature-40 ºC ... 70 ºC
Storage/transport temperature-40 ºC ... 85 ºC
Relative humidity (non-condensing)10 % ... 95 %
MTBF53.5 years (MIL-HDBK-217F)
Protective paint on PCBNo

Mechanical construction

Dimensions (W x H x D)74 mm x 131 mm x 111 mm
MountingDIN Rail
Weight410 g
Protection classIP20

Mechanical stability

IEC 60068-2-27 shock15 g, 11 ms duration, 18 shocks
IEC 60068-2-6 vibration1 mm, 2 Hz-13.2 Hz, 90 min.; 0.7 g, 13.2 Hz-100 Hz, 90 min.; 3.5 mm, 3 Hz-9 Hz, 10 cycles, 1 octave/min.; 1 g, 9 Hz-150 Hz, 10 cycles, 1 octave/min

EMC interference immunity

EN 61000-4-2 electrostatic discharge (ESD)6 kV contact discharge, 8 kV air discharge
EN 61000-4-3 electromagnetic field10 V/m (80-1000 MHz)
EN 61000-4-4 fast transients (burst)2 kV power line, 1 kV data line
EN 61000-4-5 surge voltagepower line: 2 kV (line/earth), 1 kV (line/line), 1 kV data line
EN 61000-4-6 conducted immunity3 V (10 kHz-150 kHz), 10 V (150 kHz-80 MHz)

EMC emitted immunity

FCC CFR47 Part 15FCC 47 CFR Part 15 Class A
EN 55022EN 55022 Class A

Approvals

Safety of industrial control equipmentcUL 508
Hazardous locationsISA 12.12.01 Class 1 Div. 2; ATEX 100a, Zone 2
ShipbuildingGermanischer Lloyd, DNV, RINA
Railway normEN50121-4
SubstationIEC 61850-3, IEEE 1613

Teknisk info

Produktinformasjon

Produsent Hirschmann


Tilbehør
Support
Varen er på lager.
Varen er bestilt fra leverandør og leveringsdato er bekreftet.
Varen er bestilt fra leverandør, men leveringsdato er ikke bekreftet.
Varen må bestilles fra leverandør.
Varen befinner seg på fjernlager.
Varen er bestilt fra leverandør, men leveringsdato er ikke bekreftet.
Varene bestilles fra vår leverandørs lager.
Ubekreftet - Ta kontakt med kundesenter for nærmere informasjon.