Hirschmann MACH 102-24TP-F switch 24x10/100 Mb, 2xGigabit combo

Hirschmann MACH 102-24TP-F switch

24x10/100 Mb, 2xGigabit combo

Varenr: 943 969-401
MACH 102 Industrial control room switch
 
Port type and quantity
26 ports in total; 24x (10/100 BASE-TX, RJ45) and 2 Gigabit Combo ports
 
V.24 interface 1 x RJ11 socket, serial interface for device configuration
USB interface 1 x to connect auto-configuration adapter ACA21-USB
 
Network size - cascadibility
Line - / star topology any
Ring structure (HIPER-Ring)
 
Power requirements
Operating voltage 100 - 240 VAC, 47 - 63 Hz
Power outputin Btu (IT) h 55
Rated current 0.4 - 0.2 A
 
Management
Serial Interface, web interface, SNMP V1/V2, HiVision file transfer SW HTTP/TFTP
Diagnostics: LEDs, log-file, syslog, signal contact, RMON (statistic, history, alarms, events), port mirroring, topology discovery 802.1AB, cable diagnostic
 
Configuration
Comand line interface (CLI), TELNET, BootP, DHCP, DHCP option 82, HIDiscovery, auto-configuration adapter (ACD11, ACA21-USB), Watchdog configuration, integrated DHCP server
 
Security
Port security (IP and MAC), SNMP V3, SSH, authentication (802.1x)
Redundancy functions HIPER-ring (ring structure), MRP (IEC-ring functionality), RSTP 802.1D-2004,
redundant network/ring coupling, dual homing, link aggregation
 
Filter
QoS 4 Klassen, Portpriorisierung (IEEE 802.1D/p), VLAN (IEEE 802.1Q), shared VLAN learning, Multicast (IGMP Snooping/Querier), Multicast Detection unknown Multicast, Broadcastlimiter, Fast Aging, Multicast GMRP IEEE 802.1D
 
Flow control
Flow Control 802.3x, Port Priority 802.1D/p, Priority (TOS/DIFFSERV), Prio (MAC/IP), Prio Mapping (TOS Layer2), Traffic Shaping (Unicast, Multicast, Broadcast) Ingress / Egress
 
Ambient conditions
Operating temperature 0° - +50°C
Storage/transport temperature -20° - +85°C
Relative humidity (non-condensing) 10% to 95%
 
MTBF 13.26 years (MIL-HDBK-217F Gb 25°C)
 
Mechanical construction
Dimensions (W x H x D)
448 x 310 x 44 (without fixing bracket)
Weight: 3.85 kg
 
Protection class IP20
EMC interference immunity
 
EN 61000-4-2 electrostatic discharge (ESD) 4 kV contact discharge, 8 kV air discharge
EN 61000-4-3 electromagnetic field 10 V/m (80 - 2700 MHz)
EN 61000-4-4 fast transients (burst) 2 kV power line, 4 kV data line
EN 61000-4-5 surge voltage power line: 2 kV (line/earth), 1 kV (line/line), 4 kV data line
EN 61000-4-6 conducted immunity 10 V (150 kHz - 80 MHz)
 
EMC emitted immunity
FCC CFR47 Part 15
FCC 47 CFR Part 15 Class A
EN 55022 EN 55022 Class A
 
Approvals
Safety of industrial control equipment cUL 508 (pending)