MACH 1000 Switch for Substation MAR1030-CCBBBBBBBBTTTT999999999999SCCHP

MACH 1000 Switch for Substation

MAR1030-CCBBBBBBBBTTTT999999999999SCCHP

Varenr: MAR1030-CC8xB4xTSCCH

Product description

DescriptionIndustrial managed Fast/Gigabit Ethernet Switch, 19" rack mount, fanless Design, according to IEEE 802.3, store-and-forward-switching
Port type and quantityGigabit-Ethernet ports in total: 2; 2 x Combo ports (10/100/1000BASE-TX RJ 45 plus FE/GE-SFP-slot; Fast-Ethernet ports in total: 12 x ports in total; 4 x Twisted Pair, 8 x Multimode LC;
TypeMAR1030-CCBBBBBBBBTTTT999999999999SCCHPHH08.0.
Order No.MAR1030-CCBBBBBBBBTTTT999999999999SCCHPHH08.0.

More Interfaces

Power supply/signaling contactPower supply 1: power supply 3-pin spring clip, signal contact 2-pin spring clip; Power supply 2: power supply 3-pin spring clip, signal contact 2-pin spring clip
V.24 interface1 x RJ11 socket
USB interface1 x to connect auto-configuration adapter ACA21-USB

Network size - length of cable

Twisted pair (TP)0 m ... 100 m

Network size - cascadibility

Line - / star topologyAny
Ring structure (HIPER-Ring) quantity switches100 switches

Power requirements

Operating voltagePower supply 1: 24/36/48 VDC; Power supply 2: 24/36/48 VDC
Current consumption at 24 V DCPower supply 1 and 2: 1400 mA max, if all ports are equipped with fiber

Software

ManagementSerial interface, web-interface, SNMP V1/V2, HiVision file transfer SW HTTP/TFTP, LLDP-MED, Voice VLAN
DiagnosticsLEDs, log-file, syslog, relay contact, RMON, port mirroring 1:1 and n:1, egress/ingress traffic configurable, topology discovery 802.1AB, cable tester (TX), address conflict detection, network error detection, SFP diagnostic [temperature, optical input and output power (µW and dBm)], Trap for configuration saving and changing, duplex mismatch detection, disable learning, Port Monitor
ConfigurationComand line interface (CLI), TELNET, BootP, DHCP, DHCP option 82, HIDiscovery, easy device exchange with auto-configuration adapter ACA21-USB (automatic software and/or configuration upload), automatic script load from ACA21, integrated DHCP server per port, DHCP relay, automatic invalid configuration undo, Offline Configuration, SFP Whitelist, ARC automatic ring configuration (MRP), automatic port shutdown (link flapping), configuration signature (water marking), overload detection
SecurityPort Security (IP und MAC) with multiple addresses (MAC 50 per port), SNMP V3, SSHv2, Authentication (IEEE802.1x), 802.1x Multi Client Authentication, Guest VLAN and Unauthenticated VLAN, Port based Radius VLAN assignment
Redundancy functionsHIPER-Ring, Fast HIPER-Ring, MRP, MSTP, RSTP - IEEE802.1D-2004, MRP and RSTP in parallel, link aggregation, multiple rings
FilterQoS 4 classes, priorisation (IEEE 802.1D/p), VLAN (IEEE 802.1Q), Voice VLAN, shared VLAN learning, Q-in-Q double VLAN tagging, multicast IGMP v1/v2/v3 (snooping/querier), multicast detection unknown multicast, broadcast-, unicast-, multicast limiter, fast aging, GMRP IEEE 802.1D, Jumbo Frame Support
Industrial ProfilesEtherNet/IP and PROFINET (2.2 PDEV, GSDML Stand-alone generator, automatic device exchange) profiles included, configuration and diagnostic via automation software tools like e.g. STEP7, or Control Logix IEC61850 protocol (MMS Server, Switch Model)
Time synchronisationSNTP Server, PTP / IEEE 1588, realtime clock with energy buffer
Flow controlFlow Control 802.3x, Port Priority 802.1D/p, Priority (TOS/DIFFSERV), Prio (MAC/IP), Prio Mapping (TOS Layer2), Traffic Shaping (Unicast, Multicast, Broadcast) Ingress / Egress

Ambient conditions

Operating temperature0 ºC ... 60 ºC
Storage/transport temperature-40 ºC ... 85 ºC
Relative humidity (non-condensing)10 % ... 95 %
Protective paint on PCBNo

Mechanical construction

Dimensions (W x H x D)445 mm x 44 mm x 308 mm
Mounting19" control cabinet
Weightappr. 5 kg
Protection classIP30

Mechanical stability

IEC 60068-2-27 shock15 g, 11 ms duration, 18 schocks
IEC 60068-2-6 vibration1 mm, 2 Hz - 13.2 Hz, 90 min.; 0.7g, 13,2 Hz - 100 Hz, 90 min.; 3.5 mm, 3 Hz - 9 Hz, 10 cycles, 1 octave/min.; 1g, 9 Hz - 150 Hz, 10 cycles, 1 octave/min.

EMC interference immunity

EN 61000-4-2 electrostatic discharge (ESD)8 kV contact discharge, 15 kV air discharge
EN 61000-4-3 electromagnetic field35 V/m (80 - 2700 MHz); 1kHz, 80% AM
EN 61000-4-4 fast transients (burst)4 kV power line, 4 kV data line
EN 61000-4-5 surge voltagePower line: 2 kV (line/earth), 1 kV (line/line), 1 kV data line IEEE1613: power line 5kV (line/earth)
EN 61000-4-6 conducted immunity2,5 kV (line/earth), 1 kV (line/line) (1MHz)
EN 61000-4-16 mains frequency voltage30V, 50Hz continous; 300V, 50Hz 1s

EMC emitted immunity

FCC CFR47 Part 15FCC CFR47 Part 15 Class A
EN 55022EN 55022 Class A

Approvals

Safety of industrial control equipmentcUL 508 (pending)
Hazardous locationscUL 1604 Class1 Div 2 (pending)
Germanischer LloydGermanischer Lloyd (in preparation)
SubstationIEC 61850-3; IEEE 1613
TransportationEN 50121-4, NEMA TS