Hawke 753 B-M25 Brass

Exde (0,66"-1,02") w/Compound

Varenr: 753-BM25BR
Gland Size
C2-1 1/2"NPT (1,10" - 1,61")
C2-1 1/2"NPT (1,10" - 1,61")
O-1/2"NPT (0,37"-0,63")
O-1/2"NPT (0,37"-0,63")
A-1/2"NPT (0,49" - 0,81")
A-1/2"NPT (0,49" - 0,81")
A-3/4"NPT (0,49" - 0,81")
A-3/4"NPT (0,49" - 0,81")
B-1"NPT (0,66" - 1,02")
B-1"NPT (0,66" - 1,02")
C-1 1/4"NPT (0,87" - 1,30")
C-1 1/4"NPT (0,87" - 1,30")
D-2"NPT (1,42" - 2,07")
D-2"NPT (1,42" - 2,07")
B-M25 (0,66"-1,02")
B-M25 (0,66"-1,02")
A-M20 (0,49" - 0,81")
A-M20 (0,49" - 0,81")
BeskrivelseTeknisk infoSupport
Beskrivelse

Application

Outdoor or indoor use.
For use with braid armoured marine shipboard jacketed or non-jacketed cable.

Features

Provides a barrier seal between the individual insulated conductors within the cable and prevents entry of the products of an explosion into the cable.
Assembly of the cable gland/connector compresses and distributes the compound evenly to effect a barrier seal at the point of entry into the enclosure.
Provides an outer deluge seal to prevent moisture ingress to the cable armour and enclosure. Deluge seal is coloured red to indicate hazardous locations product.
Provides a cable retention and low smoke and fume, zero halogen seal onto the cables outer jacket.

Materials & Finishes

The 753 cable gland/connector is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminum. Brass NPT entries are nickel plated as standard.

Technical Data

  1. UL Listing No:
    E84941.
  2. Suitable for use in:
    Class 1, Division 1, Gas Groups A, B , C and D.
    Class 1, Zone 2, Gas Groups IIA, IIB and IIC.
    AExd IIC and AExe II Class 1, Zone 2.
  3. Flameproof Exd IIC Gb, Increased Safety Exe IIC Gb, Dust Extb IIIC Db II 2 GD
    ExnR IIC Gc, Extc IIIC Dc  II 3 GD
  4. Certificate No's
    Sira 06ATEX1295X, Sira 07ATEX4330X and IECEx Sir 06.0082X.
  5. Suitable for use in:
    Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC.
  6. Construction and Test Standards:
    UL 2225, IEC/EN 60079-0, IEC/EN 60079-1, EC/EN 60079-7, IEC/EN 60079-15, IEC/EN 60079-31.
  7. Ingress Protection:
    IP66, IP67 and 
    IP 68  (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X.
  8. Deluge Protection to:
    DTS01
  9. Operating Temperature Range:
    -50°C to +60°C (UL) and -60°C to +80°C (ATEX / IECEx)
  10. Note: 753 cable glands are supplied dual ATEX/UL marked as standard.
  11. Assembly Instruction Sheet:
    AI 318 (UL, Sizes Os to F).
  12. AI 339 (UL, Size H).
  13. AI 373 (ATEX / IECEx).

 

CABLE GLAND SELECTION TABLE
Size
Ref.
Entry Thread
Size
Cable Acceptance Details ‘G’
Compressed
Length
Hexagon
Dimensions
NPT
*
Metric Inner Jacket / Cores Outer Jacket 'B' Braid 'C' Across
Flats
Across
Corners
Standard Option Max. Over
Cores 'D'
Max Inner
Jacket 'E'
Max. No. of
Cores
Min. Max.
Os ½" - M20² 0.35" 0.46" 6 0.22" 0.47" 0.008" / 0.013" 2.61" 0.94" 1.09"
O ½" - M20² 0.35" 0.46" 6 0.37" 0.63" 0.008" / 0.013" 2.61" 0.94" 1.09"
A ½" ¾" M20 0.43" 0.49" 10 0.49" 0.81" 0.008" / 0.013" 2.65" 1.18" 1.36"
B ¾" 1" M25 0.64" 0.72" 21 0.66" 1.02" 0.008" / 0.013" 2.75" 1.42" 1.64"
C 1" 1¼" M32 0.86" 0.97" 42 0.87" 1.30" 0.008" / 0.013" 2.93" 1.81" 2.09"
C2 1¼" 1½" M40 1.04" 1.16" 60 1.10" 1.61" 0.008" / 0.013" 3.15" 2.17" 2.50"
D 2" 1½" M50 1.46" 1.64" 80 1.42" 2.07" 0.008" / 0.013" 3.14" 2.56" 2.96"
E 2½" 2" M63 1.88" 2.11" 100 1.81" 2.57" 0.008" / 0.013" 3.42" 3.15" 3.64"
F 3" 2½" M75 2.32" 2.61 / 2.57" ¹ 120 2.24" 3.07" 0.008" / 0.013" 3.61" 3.74" 4.31"
3½" - M90 2.79" 3.05" 120 3.07" 3.52" 0.008" / 0.013" 3.54" 4.18" 4.84"
All dimensions in inches (except * where dimensions are in millimetres). Os - F size metric entry threads are 1.5mm pitch as standard, 15mm length of thread. For H size glands, a 2mm pitch is supplied as standard, 20mm length of thread (1.5mm pitch with 15mm length of thread can be supplied) please specify when ordering

¹ Smaller value is applicable when selecting standard NPT entry option.
² Sizes Os and O are available with an M16 thread size. For O size with M16 thread, the maximum cable inner jacket diameter is 0.43”
³ UL approved only.

Teknisk info

Produktinformasjon

Produsent Hawke International


Support
Varen er på lager.
Varen er bestilt fra leverandør og leveringsdato er bekreftet.
Varen er bestilt fra leverandør, men leveringsdato er ikke bekreftet.
Varen må bestilles fra leverandør.
Varen befinner seg på fjernlager.
Varen er bestilt fra leverandør, men leveringsdato er ikke bekreftet.
Varene bestilles fra vår leverandørs lager.
Ubekreftet - Ta kontakt med kundesenter for nærmere informasjon.